Messages & diagnostics
8.4 Faults and remedial actions of the 3RW51 soft starter
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
125
Error
No.
1)
Fault
Cause
Remedy
Manual
RESET
Remote
RESET
Auto
RESET
1466
Contact 1 failed
Power
semiconductor
defective
Check the contact blocks
for L1, L2, and L3 and
replace any that are
defective.
-
-
-
1467
Contact 2 failed
1468
Contact 3 failed
1479
Phase angle control
failure
•
Error occurs
without motor
starting:
–
Motor
terminals
are
incorrectly
connected.
–
Error in
configuratio
n of inside-
delta
circuit.
–
There is a
ground
fault.
•
Fault occurs
during starting:
–
Chosen
starting
voltage too
high
•
Network
disturbances
like harmonic
distortions
•
Check and correct the
wiring.
•
Adjust parameters.
•
Check if there are other
devices installed in the
same network that
might be generating
network disturbances
and use corresponding
filters.
x
x
-
1482
Current measuring
range exceeded
•
With sensors:
The measured
value has
exceeded the
range limits.
•
With actuators:
The output
value has
exceeded an
upper limit
value.
Check the interaction
between the module and
the sensor or actuator.
x
x
-
Содержание 3RW51 Series
Страница 142: ...Maintenance and servicing 9 5 Restore factory setting 3RW51 Soft Starter 142 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 146: ...Dimension drawings 11 1 CAx data 3RW51 Soft Starter 146 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 148: ...Circuit diagrams 12 1 CAx data 3RW51 Soft Starter 148 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 169: ...Example circuits A 2 Control circuit connection 3RW51 Soft Starter Manual 06 2019 A5E37108631002A RS AB 002 169 ...
Страница 190: ...Glossary 3RW51 Soft Starter 190 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 192: ...Index 3RW51 Soft Starter 192 Manual 06 2019 A5E37108631002A RS AB 002 ...