Example circuits
A.1 Main circuit connection
3RW51 Soft Starter
152
Manual, 06/2019, A5E37108631002A/RS-AB/002
A.1.4
Inside-delta circuit
The inside-delta circuit requires a motor with windings that can be connected in a delta
circuit where a line voltage prevails.
If the 3RW51 soft starter is operated in an inside-delta circuit, the motor power output of the
individual devices is increased by a factor of root 3. On the front of the device behind the
hinged cover, you will find a value table with increase current values for an inside-delta
circuit.
If the load voltage is connected and the motor is connected to the device, the 3RW51 soft
starter automatically detects the connection type.
Motor rotation in line phase direction