Example circuits
A.1 Main circuit connection
3RW51 Soft Starter
150
Manual, 06/2019, A5E37108631002A/RS-AB/002
A.1.2
Feeder assembly, type of coordination 1 with fuses
If a main or line contactor is used, it should not be connected between the soft starter and
the motor. The soft starter could otherwise indicate a "Missing load voltage" fault in case of a
start command and delayed connection of the contactor.
Feeder assembly, type of coordination 1 with fuses
If galvanic isolation is required, install a motor contactor between the soft starter and the
fuses protector.
F1
gG full-range fuse for cable and line protection (e.g. 3NA3)
Q12 Motor contactor for electrical decoupling
Q21 External bypass contactor
Q11 3RW51 soft starter
M1
Motor
PE
Protective conductor