Parameter assignment
5.6 RESET MODES
3RW51 Soft Starter
76
Manual, 06/2019, A5E37108631002A/RS-AB/002
5.6
RESET MODES
Note
Effects of RESET MODE.
Setting of the RESET MODE will only affect acknowledgment response of the motor
overload protection.
You will find more information in Chapter Faults and remedial actions of the 3RW51 soft
starter (Page 123) with the comment "Depends on parameter RESET MODE".
Manual RESET
"Manual RESET" means that the following options are available for acknowledging faults:
●
RESET / TEST key on 3RW51 soft starter
●
RESET / TEST key on 3RW5 HMI Standard
●
Reset via bus interface
●
Reset via F key on 3RW5 HMI High Feature
●
Reset via 3RW5 HMI High Feature
Remote RESET
"Remote RESET" means that faults are acknowledged by switching the control supply
voltage off and on again. The control supply voltage on the 3RW51 soft starter must be
switched off for at least 4 s.
Auto RESET
"Auto RESET" means that faults are automatically reset as soon as the cause is eliminated.
Содержание 3RW51 Series
Страница 142: ...Maintenance and servicing 9 5 Restore factory setting 3RW51 Soft Starter 142 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 146: ...Dimension drawings 11 1 CAx data 3RW51 Soft Starter 146 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 148: ...Circuit diagrams 12 1 CAx data 3RW51 Soft Starter 148 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 169: ...Example circuits A 2 Control circuit connection 3RW51 Soft Starter Manual 06 2019 A5E37108631002A RS AB 002 169 ...
Страница 190: ...Glossary 3RW51 Soft Starter 190 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 192: ...Index 3RW51 Soft Starter 192 Manual 06 2019 A5E37108631002A RS AB 002 ...