Wiring
4.1 Connections
3RW51 Soft Starter
54
Manual, 06/2019, A5E37108631002A/RS-AB/002
④
A1 / A2: Supply voltage for control terminals
⑤
Input IN to switch the drive on and off
⑥
Output 13, 14: To signal the operating state ON or RUN (parameterizable)
⑦
Output 23, 24: To signal the operating state BYPASSED
⑧
Output 95, 96 and 98: To signal faults
⑨
Analog outputs AQ-, AQ I+ und AQ U+: Connection of an evaluation unit to display the motor
current (optional)
•
AQ- / AQ U+: For evaluation units with output signal type Voltage, signal range 0 - 10 V
•
AQ- / AQ I+: For evaluation units with output signal type Current, signal range 4 - 20 mA
(factory setting)
Note
Parameterizing output 13 / 14
You will find more information on parameterization in Chapter Parameterizing output 13 / 14
(output signal ON or RUN) (Page 77).
Note
Parameterizing the analog output
You can parameterize the output of the analog output with the 3RW5 HMI High Feature
(Page 109).
Содержание 3RW51 Series
Страница 142: ...Maintenance and servicing 9 5 Restore factory setting 3RW51 Soft Starter 142 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 146: ...Dimension drawings 11 1 CAx data 3RW51 Soft Starter 146 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 148: ...Circuit diagrams 12 1 CAx data 3RW51 Soft Starter 148 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 169: ...Example circuits A 2 Control circuit connection 3RW51 Soft Starter Manual 06 2019 A5E37108631002A RS AB 002 169 ...
Страница 190: ...Glossary 3RW51 Soft Starter 190 Manual 06 2019 A5E37108631002A RS AB 002 ...
Страница 192: ...Index 3RW51 Soft Starter 192 Manual 06 2019 A5E37108631002A RS AB 002 ...