Parameter assignment
5.8 Analog output
3RW51 Soft Starter
78
Manual, 06/2019, A5E37108631002A/RS-AB/002
Note
If you do not press any key at all for more than 10 seconds in programming mode, the device
automatically terminates programming mode and reverts to normal operation.
Tip
Alternatively, output 13 / 14 may also be set in the "Parameters > Soft Starter > ON / RUN
relay output" menu of the 3RW5 HMI High Feature (accessories).
5.8
Analog output
Note
You may change the default parameters of the analog output with the 3RW5 HMI High
The analog output provides the present motor current "I" as a percentage, independent of
the connection type. Depending on the selected parameter, the signal can either be output
as current or as voltage.
Depending on the selected signal, connecting terminals are available on the 3RW51 soft
starter.
●
Measuring range of current output: 4 - 20 mA (default setting)
●
Measuring range of voltage output: 0 - 10 V (default setting)