Wiring
4.8 Replacing the control terminals
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
65
4.8
Replacing the control terminals
Requirements
●
Remove the cover over the control cable duct. (Page 68)
●
Control terminal as spare part (screw terminal: 3RW5980-1TR00)
Dismantling procedure
DANGER
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
●
Press against the lock
①
and pull the control terminal out
②
.