Data sets
A.3 DS68 Read/write process image output
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
177
A.3
DS68 Read/write process image output
Note
Please note that data set 68 is overwritten by the cyclic process image in automatic mode!
Byte
Content
Value / value range
Meaning
0
Coordination
0x21
Write via acyclic bus channel (PLC)
1
Reserved
0x00
-
2
Reserved
0x00
-
3
Reserved
0x00
-
Process image of the outputs
4
Process data
DQ 0.0 to DQ 0.7
See table below
5
Process data
DQ 1.0 to DQ 1.7
See table below
Table A- 1
Content of process image of the outputs (in bytes 4 and 5)
Byte.Bit
Encoding
Process data
Meaning
Relevant for
4.0
Bit (1 = active)
DQ 0.0
Motor CW
All
4.1
DQ 0.1
Motor CCW
Reversing starters only
4.2
DQ 0.2
-
-
4.3
DQ 0.3
Trip reset
All
4.4
DQ 0.4
Emergency start
All
1)
4.5
DQ 0.5
-
-
4.6
DQ 0.6
-
-
4.7
DQ 0.7
Cold start
All
2)
5.0
Bit (1 = active)
DQ 1.0
-
-
5.1
DQ 1.1
-
-
5.2
DQ 1.2
-
-
5.3
DQ 1.3
-
-
5.4
DQ 1.4
-
-
5.5
DQ 1.5
-
-
5.6
DQ 1.6
-
-
5.7
DQ 1.7
Disable quick stop
All
1) Not for EX motor
2) F starter as of FW V 1.2.0
Содержание 3RK1308-0 00-0CP0 Series
Страница 1: ...Motor starter 3RK1308 0 00 0CP0 ...
Страница 2: ......
Страница 10: ...Introduction Motor starter 3RK1308 0 00 0CP0 10 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 16: ...Security information Motor starter 3RK1308 0 00 0CP0 16 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 34: ...Documentation guide Motor starter 3RK1308 0 00 0CP0 34 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 174: ...CAx data 10 1 CAx data Motor starter 3RK1308 0 00 0CP0 174 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 204: ...Data sets A 16 I M data Motor starter 3RK1308 0 00 0CP0 204 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 218: ...Index Motor starter 3RK1308 0 00 0CP0 218 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...