Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
139
Parameters/address space
7
7.1
Parameter assignment
When configuring an ET 200SP motor starter, the full parameterization scope is set and
automatically transferred to the motor starter. When parameterizing in the user program, the
parameters are transferred to the module via the data sets with the statement "WRREC". If
the CPU initiates a new parameter assignment, e.g. if communication breaks down, the
parameterization is overwritten by the system parameterization via the user program.
The modules of the ET 200SP distributed I/O system support the full parameterization scope
of the ET 200SP motor starters.
Note
List of supported ET 200SP header modules
You will find a list of the compatible ET 200SP header modules in the
Siemens Industry Online Support
https://support.industry.siemens.com/cs/ww/en/view/109485777
Note
Reduction to default parameters
In the following cases, the full scope of parameterization is reduced by the configuring
software to the standard parameters (DS201) for system reasons:
•
Activated DPV0 alarm mode (in the case of PROFIBUS IMs)
•
Activated option handling (in the case of PROFIBUS IMs)
•
When configuring using a GSD (for parameters, see
Read/write DS201 device parameter 1 (Page 193))
Note
Trip RESET
When you send valid parameters to the motor starter, a trip RESET is triggered.
Acknowledgeable active faults are deleted.
Содержание 3RK1308-0 00-0CP0 Series
Страница 1: ...Motor starter 3RK1308 0 00 0CP0 ...
Страница 2: ......
Страница 10: ...Introduction Motor starter 3RK1308 0 00 0CP0 10 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 16: ...Security information Motor starter 3RK1308 0 00 0CP0 16 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 34: ...Documentation guide Motor starter 3RK1308 0 00 0CP0 34 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 174: ...CAx data 10 1 CAx data Motor starter 3RK1308 0 00 0CP0 174 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 204: ...Data sets A 16 I M data Motor starter 3RK1308 0 00 0CP0 204 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 218: ...Index Motor starter 3RK1308 0 00 0CP0 218 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...