Parameters/address space
7.7 Assigning fail-safe motor starter parameters
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
151
7.7.3
Configuring ATEX operation
ET 200SP fail-safe motor starters protect motors in an ATEX environment. The following
parameters are considered to be safety-related in ATEX operation:
●
Rated operational current (I
e
)
●
Trip class
You set the parameters via the data sets or using the engineering software.
Before the new safety-related parameters are accepted, however, check and confirm the
new parameters. The parameter settings are indicated by means of a flashing sequence of
the LEDs on the fail-safe motor starter. As soon as you have ensured with the aid of the
LEDs that all parameters are correctly set, confirm the new parameters on the device by
means of the blue button. The parameters are not accepted until you have confirmed and the
motor starter is "Ready for motor ON". Changes to parameters that are not safety-related do
not require confirmation.
Содержание 3RK1308-0 00-0CP0 Series
Страница 1: ...Motor starter 3RK1308 0 00 0CP0 ...
Страница 2: ......
Страница 10: ...Introduction Motor starter 3RK1308 0 00 0CP0 10 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 16: ...Security information Motor starter 3RK1308 0 00 0CP0 16 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 34: ...Documentation guide Motor starter 3RK1308 0 00 0CP0 34 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 174: ...CAx data 10 1 CAx data Motor starter 3RK1308 0 00 0CP0 174 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 204: ...Data sets A 16 I M data Motor starter 3RK1308 0 00 0CP0 204 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 218: ...Index Motor starter 3RK1308 0 00 0CP0 218 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...