Alarms/diagnostic messages
8.1 Status and error displays
Motor starter (3RK1308‑0**00‑0CP0)
166
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
LED combinations
Table 8- 6
Status displays ST/OL/MAN/PWR
LEDs
Meaning
Explanation
ST/OL
(State/
Overload)
MAN
(Manual)
PWR
(Power)
Lights up
for 4 s
Lights up
for 4 s
Lights up
for 4 s
LED/fan test
All LEDs are switched on for 4 s
(triggered by pressing the blue button).
Flashes
Flashes
Lights up
Firmware update active or canceled
-
OFF
OFF
OFF
No supply voltage
No supply voltage available
A detected undervoltage (in the case of
still functioning electronics) is not
reported as power OFF, but as a fault.
Flashes
at 1 Hz
Flashes
Lights up
Device fault
Non-correctable fault detected following
self-diagnostics (contactor contacts,
switching element, etc.).
Remedy: Check the wiring and, if
necessary, replace the device.
Содержание 3RK1308-0 00-0CP0 Series
Страница 1: ...Motor starter 3RK1308 0 00 0CP0 ...
Страница 2: ......
Страница 10: ...Introduction Motor starter 3RK1308 0 00 0CP0 10 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 16: ...Security information Motor starter 3RK1308 0 00 0CP0 16 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 34: ...Documentation guide Motor starter 3RK1308 0 00 0CP0 34 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 174: ...CAx data 10 1 CAx data Motor starter 3RK1308 0 00 0CP0 174 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 204: ...Data sets A 16 I M data Motor starter 3RK1308 0 00 0CP0 204 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 218: ...Index Motor starter 3RK1308 0 00 0CP0 218 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...