Functions
6.21 Quick Stop direction-independent
Motor starter (3RK1308‑0**00‑0CP0)
122
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Example 2: Input 1 signal = non-retentive
①
The motor is switched on and off by "Motor CW".
②
The motor is switched on by "Motor CW", then switched off by the level at digital input 1
(parameterized with input action 1 = Quick Stop). The Quick Stop function is reset by Disable
quick stop. The motor is switched on again since "Motor CW" is still active.
③
The motor is switched off by the level at digital input 1. The "Quick Stop" function is reset by
setting "Disable quick stop". As the level "Motor CW" is still active, the motor runs "CW" again
until the "Disable quick stop" command is revoked.
④
Motor is switched on by "Motor CW", then switched off by the level at digital input 1. While the
"Quick Stop" function is active, the motor remains switched off and starts up again when
"Quick Stop" is revoked until "Motor CW" is switched off.
Содержание 3RK1308-0 00-0CP0 Series
Страница 1: ...Motor starter 3RK1308 0 00 0CP0 ...
Страница 2: ......
Страница 10: ...Introduction Motor starter 3RK1308 0 00 0CP0 10 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 16: ...Security information Motor starter 3RK1308 0 00 0CP0 16 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 34: ...Documentation guide Motor starter 3RK1308 0 00 0CP0 34 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 174: ...CAx data 10 1 CAx data Motor starter 3RK1308 0 00 0CP0 174 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 204: ...Data sets A 16 I M data Motor starter 3RK1308 0 00 0CP0 204 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 218: ...Index Motor starter 3RK1308 0 00 0CP0 218 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...