Functions
6.7 Substation monitoring
Motor
starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
95
6.7.4
Blocking time and blocking current
The blocking current specifies how much current is consumed by the motor (at rated voltage)
when the drive is blocked.
If the motor current exceeds 400 % of the set motor current I
e
for a time > 1 s after the motor
ramps up, the blocking protection is tripped and a trip command is generated.
After the motor is switched on, the parameterized values for the blocking current and
blocking time apply. A switchover to the fixed values (400 %, 1 s) takes place depending on
the set motor protection class (CLASS 5/ 10 A
→
5 s, CLASS 10, off
→
10 s).
●
The "Tripping due to motor blocking" and "Group fault" diagnostic messages are
generated
●
The statistic "Number of motor overload trips" is incremented by 1
If the parameter "Group fault diagnostics" is set to "Enabled", a corresponding diagnostic
interrupt is set if blocking protection responds.
Setting ranges
The table below shows the possible setting range for the blocking current and the blocking
time:
Device parameters
Default setting
Setting range
Blocking current
800 %
150 ... 1500 % of I
e
Increment: 50 %
Blocking time
1 s
1 ... 7.5 s
Increment: 0.5 s
6.7.5
Device protection model
To protect the switching elements in the main circuit against impermissible operating states,
an integrated intrinsic device protection is provided in the upper load range. The device
protection model consists of the relay protection model (dotted line) and the thermal motor
model (continuous line) with the highest permissible current setting. The device protection is
active 20 ms after the ON command. This means that, in the case of ET 200SP motor
starters, an overload trip may occur in the upper current range before the motor protection
trips. The device protection is active even when the overload protection is set to "Warn" and
the "Response of the thermal motor model on restart" parameter is set to "Delete".
Содержание 3RK1308-0 00-0CP0 Series
Страница 1: ...Motor starter 3RK1308 0 00 0CP0 ...
Страница 2: ......
Страница 10: ...Introduction Motor starter 3RK1308 0 00 0CP0 10 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 16: ...Security information Motor starter 3RK1308 0 00 0CP0 16 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 34: ...Documentation guide Motor starter 3RK1308 0 00 0CP0 34 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 174: ...CAx data 10 1 CAx data Motor starter 3RK1308 0 00 0CP0 174 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 204: ...Data sets A 16 I M data Motor starter 3RK1308 0 00 0CP0 204 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 218: ...Index Motor starter 3RK1308 0 00 0CP0 218 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...