72
4 FUNCTIONS
4.5 AND link
4.5
AND link
This function connects each input of an FX5-SF-MU4T5 and FX5-SF-8DI4 using AND logic.
Setting method
■
For FX5-SF-MU4T5
Set the FUNCTION rotary switch to '5', '6', '7', or '9'.
Sensors that can be connected to an FX5-SF-MU4T5 are as follows.
: Connectable,
: Not connectable
FX5-SF-MU4T5
(Program)
Inputs and sensors
Description
Input of logic
path A (I0, I1)
Input of logic
path B (I2, I3)
5
: Potential free contact
Dual-channel equivalent N/C contact (with
cross-circuit detection)
•
: Emergency stop button
•
: Safety door switch
Dual-channel equivalent N/C contact (with
cross-circuit detection)
: Two-hand control switches
Two-hand operation (
A) without jog mode
: Two-hand control switches
Two-hand operation (
A) with jog mode (time
limit 5 seconds)
: Non-contact safety switch
Dual-channel equivalent N/C contact
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact (with
cross-circuit detection)
6
: Potential free contact
Dual-channel equivalent N/C contact (with
cross-circuit detection)
•
: Emergency stop button
•
: Safety door switch
Dual-channel equivalent N/C contact (with
cross-circuit detection)
: Non-contact safety switch
Dual-channel equivalent N/C contact
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact (with
cross-circuit detection)
7
•
: Potential free contact
•
: Emergency stop button
•
: Safety door switch
Single-channel N/C contact
•
: Potential free contact
•
: Emergency stop button
•
: Safety door switch
Dual-channel equivalent N/C contact
: Electro-sensitive protective
equipment (ESPE)
Electro-sensitive protective equipment
(ESPE) with semiconductor output
: Inductive switch
Sensor with semiconductor output (OSSD
output)
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact
9
•
: Potential free contact
•
: Emergency stop button
•
: Safety door switch
Single-channel N/C contact
•
: Potential free contact
•
: Emergency stop button
•
: Safety door switch
Dual-channel equivalent N/C contact
: Potential free contact
Dual-channel equivalent N/C contact (with
cross-circuit detection)
•
: Emergency stop button
•
: Safety door switch
Dual-channel equivalent N/C contact (with
cross-circuit detection)
: Electro-sensitive protective
equipment (ESPE)
Electro-sensitive protective equipment
(ESPE) with semiconductor output
: Non-contact safety switch
Dual-channel equivalent N/C contact
: Inductive switch
Sensor with semiconductor output (OSSD
output)
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact
: Single-beam photoelectric safety
sensor
Dual-channel equivalent N/C contact (with
cross-circuit detection)
Содержание MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Страница 2: ......
Страница 29: ...1 OVERVIEW 27 1 MEMO ...
Страница 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Страница 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Страница 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Страница 169: ...APPX Appendix 6 How to Use MELSEC iQ F Series Safety Extension Module Configuration Guide 167 A MEMO ...
Страница 171: ...I 169 MEMO ...
Страница 175: ......