132
APPX
Appendix 2 Standards
*1 FX5-SF-MU4T5s and FX5-SF-8DI4s are open-type devices (devices designed to be housed inside other equipment) intended to be
placed in a conductive control panel. The tests were conducted with the device installed in a control panel.
EC declaration of conformity
EN61000-4-16
Immunity to conducted, common mode
disturbances
Low-frequency noise is applied to power lines and
signal lines.
• AC power
1.5 k to 15 kHz: 1 to 10 V, 20 dB/Dec.
15 k to 150 kHz: 10 V
• DC power
1.5 k to 15 kHz: 1 to 10 V, 20 dB/Dec.
15 k to 150 kHz: 10 V
DC, 16 2/3 Hz, 50/60 Hz: 10 V continuous, 100 V
for a short time (1s)
150/180 Hz: 10 V continuous
• I/O signal/control
1.5 k to 15 kHz: 1 to 10 V, 20 dB/Dec.
15 k to 150 kHz: 10 V
DC, 16 2/3 Hz, 50/60 Hz: 10 V continuous, 100 V
for a short time (1s)
150/180 Hz: 10 V continuous
Test item
Test description
Value specified in standard
We,
Manufacturer
:
MITSUBISHI ELECTRIC CORPORATION
Address
(Place of Declare)
:
TOKYO 100-8310, JAPAN
Brand Name
:
declare under our sole responsibility that the product
Description
:
Programmable Controller
Type of Model
:
MELSEC iQ-F Series FX5
Notice
:
Refer to next page about each type name
to which this declaration relates is in conformity with the following standard and directive.
Directive
Harmonized Standard
Notified Body
EMC Directive
2014/30/EU
EN61131-2 2007
-
Machinery Directive
2006/42/EU
EN ISO 13849-1 2015
1
RoHS Directive
2011/65/EU
EN50581 2012
EN62321 2009
-
This declaration is based on the conformity assessment of following Notified Body
No.
Name and Address
Identification
Number
Issued certificate No.
1
TÜV SÜD Product Service GmbH
Ridlerstraße 65, 80339 Munich, Germany
0123
M6A 083244 0001
EU DECLARATION OF CONFORMITY
APPENDIX List of type name to declare
FX5-SF-8DI4
FX5-SF-MU4T5
Содержание MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Страница 2: ......
Страница 29: ...1 OVERVIEW 27 1 MEMO ...
Страница 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Страница 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Страница 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Страница 169: ...APPX Appendix 6 How to Use MELSEC iQ F Series Safety Extension Module Configuration Guide 167 A MEMO ...
Страница 171: ...I 169 MEMO ...
Страница 175: ......