30
2 SPECIFICATIONS
2.4 Performance Specifications
2.4
Performance Specifications
The following shows the performance specifications.
Safety inputs of an FX5-SF-MU4T5
*1 The minimum switch-off time is the minimum time takes until a switch-off condition is detected after a module is switched off.
*2 A response time without any sensors. When sensors are connected, the data of the connected sensors is applied and the minimum
switch-off time is extended.
*3 The time from when a muting condition is enabled (I2/I3 are turned ON) until a muting function is activated.
*4 Indicates the maximum switch-off time when a muting error occurs.
*5 A muting input (I2 or I3) keeps OFF for the specified period of time.
*6 A time from when an ERROR LED starts flashing.
General inputs of an FX5-SF-MU4T5
Item
Specification
Number of inputs
4 points
Input voltage (ON)
13 VDC to 30 VDC
Input voltage (OFF)
-5 VDC to 5 VDC
Input current (ON)
3 mA (2.4 mA to 3.8 mA)
Input current (OFF)
-2.5 mA to 2.1 mA
Input response time (filter delay)
2 ms
Indication of input operation
LED lights when an input is ON.
Minimum switch-off time
(I0/I1)
Program 1, 2, 4, 5, 6, and 9
24 ms
Program 3.1, 7, and 8
4 ms
Program 3.2
76 ms/24 ms
Minimum switch-off time
(I2/I3)
Program 4, 5, and 6
24 ms
Program 1, 2, 3, 7, 8, and 9
4 ms
Power-up time
70 ms
Synchronous time monitoring
Program 1 and 2
1500 ms
Program 4 and 5
500 ms
Muting ON
Program 3
61 ms
Muting OFF
Program 3
61 ms (165 ms
Muting gap suppression
Program 3
94 ms to 100 ms
Reset time
106 ms
Maximum teach-in time of the ENTER button
3 s
Duration of actuation of a reset button (X0 and X1)
50 ms to 5 s
Item
Specification
Number of inputs
4 points (3 general inputs/1 ENABLE input)
Input voltage (ON)
13.0 VDC to 30.0 VDC
Input voltage (OFF)
-5.0 VDC to 5.0 VDC
Input current (ON)
3 mA (2.4 mA to 3.8 mA)
Input current (OFF)
-2.5 mA to 2.1 mA
Indication of input operation
LED lights when an input is ON.
Minimum switch-off time (XS0)
4 ms
Содержание MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Страница 2: ......
Страница 29: ...1 OVERVIEW 27 1 MEMO ...
Страница 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Страница 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Страница 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Страница 169: ...APPX Appendix 6 How to Use MELSEC iQ F Series Safety Extension Module Configuration Guide 167 A MEMO ...
Страница 171: ...I 169 MEMO ...
Страница 175: ......