APPX
Appendix 5 Buffer Memory
147
A
Module name identifier
A module name identifier is stored.
■
Buffer memory address
The buffer memory address of this area is as follows.
■
Module name identifier
Lower rotary switch startup state
The information of the rotary switches that have been set at startup is stored.
■
Buffer memory address
The buffer memory address of this area is as follows.
■
Startup state
FX5-SF-MU4T5
FX5-SF-8DI4
Buffer memory name
Address
1st Module Module name identifier
113
2nd Module Module name identifier
153
3rd Module Module name identifier
193
Bit
Name
Description
b0
Module name identifier
1: FX5-SF-MU4T5
3: FX5-SF-8DI4
b1
b2
b3
b4
b5
b6
b7
b8 to b15
Fixed to 0
Buffer memory name
Address
1st Module Lower Rotary Switch startup state
115
2nd Module Lower Rotary Switch startup state
155
3rd Module Lower Rotary Switch startup state
195
Bit
Name
Description
b0
DELAY setting
0: 0s
1: 0.5s
2: 1s
3: 1.5s
4: 2s
5: 2.5s
6: 3s
7: 3.5s
8: 4s
9: 5s
b1
b2
b3
b4 to b15
Fixed to 0
Bit
Name
Description
b0
INPUT B
0: Disabled (Input signals are ignored.)
1 to 9: 1 to 9 logic
b1
b2
b3
b4 to b15
Fixed to 0
Содержание MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Страница 2: ......
Страница 29: ...1 OVERVIEW 27 1 MEMO ...
Страница 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Страница 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Страница 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Страница 169: ...APPX Appendix 6 How to Use MELSEC iQ F Series Safety Extension Module Configuration Guide 167 A MEMO ...
Страница 171: ...I 169 MEMO ...
Страница 175: ......