8 PROGRAMMING
8.2 Programming Method (for FX5-SF-MU4T5/FX5-SF-8DI4)
8.2
Programming Method (for FX5-SF-MU4T5/FX5-SF-
8DI4)
Select a program by turning the rotary switch on the safety extension module.
For details on the programs, refer to the following section.
Page 40 Built-In Program Selection Function
The settings can be checked in MELSEC iQ-F Series Safety Extension Module Configuration Guide
Page 151 How to Use MELSEC iQ-F Series Safety Extension Module Configuration Guide
After wiring external devices and selecting a program, apply the setting.
Applying a setting
1.
Wire external devices to the safety extension module.
2.
While pressing the ENTER button on FX5-SF-MU4T5, turn ON the power of the FX5 CPU module and the safety
extension module simultaneously (within two seconds).
3.
When the ERROR LED of FX5-SF-MU4T5 begins to flash, release the ENTER button within three seconds.
4.
Turn OFF the power of the FX5 CPU module and the safety extension module, and turn the powers ON again
simultaneously.
Confirm that no error occurs.
When an error occurs, check the wiring and apply the setting again.
The setting can be applied by turning ON an external power supply of the safety extension module. When an
error occurred by turning ON the power supply of an FX5 CPU module and the safety extension module
simultaneously, the error details can be checked in the GX Works3 module diagnostics screen.
Precautions
• While applying the settings, do not press the reset button connected to any of the X0, X1, or X2 terminal.
• Set a control function (restart interlock, external device monitoring (EDM), or retriggering) depending on the wiring of an X0,
X1, or X2 terminal. (
Page 95 External Wiring Example)
• When the ERROR LED begins to flash, release the ENTER button within three seconds. Otherwise, all the safety extension
modules will be in error.
• If the wiring status of the X0, X1, or X2 terminal is changed after applying the settings, an error will occur.
• Before changing the applied settings, check if the function of a protective equipment works properly. Observe the
considerations for inspection of a connected protective equipment.
FX5-SF-MU4T5
FX5-SF-8DI4
Содержание MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Страница 2: ......
Страница 29: ...1 OVERVIEW 27 1 MEMO ...
Страница 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Страница 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Страница 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Страница 169: ...APPX Appendix 6 How to Use MELSEC iQ F Series Safety Extension Module Configuration Guide 167 A MEMO ...
Страница 171: ...I 169 MEMO ...
Страница 175: ......