8 PROGRAMMING
8.3 Programming Method (for FX5 CPU module)
113
8
8.3
Programming Method (for FX5 CPU module)
A sequential program is not required because a program for a safety control can be selected using a rotary switch.
When using safety control information in a general control program, use the buffer memory of an FX5-SF-MU4T5 where the
safety control information is stored.
Program example
The following shows a program example when using safety control information in a general control program.
■
Buffer memory of an FX5-SF-MU4T5 used in the program example
■
A program example that sets an interlock depending on the status of a safety control
■
A program example that manages output status of a safety control with an annunciator
The following shows a program example for a general control that manages safety output status with an annunciator (F).
If the FX5-SF-MU4T5 detects a danger and any of the safety outputs are turned OFF, the annunciator number 5 turns ON in
the ladder program.
When all the safety outputs are turned ON, the annunciator number 5 is turned OFF.
Precautions
When starting the safety extension module, a CPU module program may start before the safety outputs of FX5-SF-MU4T5
turn ON.
Add a wait processing program as necessary as shown in the above program example.
Buffer memory name
Device
Purpose
Status when the device is ON
Input signals
U1/G69.0
Module READY
FX5-SF-MU4T5 initial processing is
completed.
U1/G69.1
Module Safety READY
Safety control works properly.
U1/G69.F
Error flag
An error occurred.
1st Module Output signal and Internal
error
U1/G102.0
Output statuses from Q2 and Q3 on
an FX5-SF-MU4T5
Outputs from Q2 and Q3 are ON.
U1/G102.1
Output statuses from Q0 and Q1 on
an FX5-SF-MU4T5
Outputs from Q0 and Q1 are ON.
Содержание MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Страница 2: ......
Страница 29: ...1 OVERVIEW 27 1 MEMO ...
Страница 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Страница 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Страница 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Страница 169: ...APPX Appendix 6 How to Use MELSEC iQ F Series Safety Extension Module Configuration Guide 167 A MEMO ...
Страница 171: ...I 169 MEMO ...
Страница 175: ......