28
2 SPECIFICATIONS
2.1 General Specifications
2
SPECIFICATIONS
This chapter explains the specifications of a safety extension module.
2.1
General Specifications
The following shows the specifications of a safety extension module.
The general specifications other than below are the same as those of the CPU module to be connected.
For the general specifications, refer to the following:
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
Dielectric withstand voltage test and insulation resistance test
Perform dielectric withstand voltage test and insulation resistance test at the following voltages between each terminal and
the safety extension module ground terminal.
Wire the terminals with caution since each terminal is not insulated.
2.2
Safety Specifications
The following shows the safety-related parameters of a safety extension module.
Item
Specification
Electromagnetic Compatibility (EMC)
EN 61000-6-2, EN 61131-2, DIN EN 61326-3-1, EN 55011 (class A)
Between terminals
Dielectric withstand voltage
Insulation resistance
Between the power supply terminal of safety extension module (DC power
supply) and CPU module ground terminal
500 VAC for one minute
10 M
Ω
or higher by 500 VDC
insulation resistance tester.
Between safety extension module input terminal and CPU module ground
terminal
Between safety extension module output terminal and CPU module ground
terminal
Item
Specification
Safety integrity level
SIL3 (IEC 61508)/SILCL 3 (IEC 62061)
Category
Category 4 (DIN EN ISO 13849-1)
Performance level
PL e(DIN EN ISO 13849-1)
PFHd
1.5
×
10
-9
to 1.5
×
10
-8
T
M
(mission time)
20 years (EN ISO 13849-1)
Содержание MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Страница 2: ......
Страница 29: ...1 OVERVIEW 27 1 MEMO ...
Страница 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Страница 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Страница 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Страница 169: ...APPX Appendix 6 How to Use MELSEC iQ F Series Safety Extension Module Configuration Guide 167 A MEMO ...
Страница 171: ...I 169 MEMO ...
Страница 175: ......