2 SPECIFICATIONS
2.5 Safety Output Derating Curve
Safety inputs of an FX5-SF-8DI4
Test outputs of an FX5-SF-8DI4
*1 A cross-circuit detection is performed only in the module.
Response time of FX5-SF-8DI4
2.5
Safety Output Derating Curve
The following figure shows the derating curve for safety outputs (Q0 to Q3) of an FX5-SF-MU4T5.
Item
Specification
Number of inputs
8 points
Input voltage (ON)
13 VDC to 30 VDC
Input voltage (OFF)
-5 VDC to 5 VDC
Input current (ON)
3 mA (2.4 mA to 3.8 mA)
Input current (OFF)
-2.5 mA to 2.1 mA
Indication of input operation
LED lights when an input is ON.
Minimum switch-off time
Program 1, 2, 3, 4, 5, and 8
24 ms
Program 6 and 7
4 ms
Synchronous time monitoring
Program 3 and 5
1500 ms
Power-up time
70 ms
Item
Specification
Number of outputs
8 points
Output method
Source output, short-circuit protection, cross-circuit detection
Output voltage
16 VDC to 30 VDC
Output current
30 mA
Test cycle
40 ms
Item
Specification
Response time
Program 1, 2, 3, 4, 5, and 8
33 ms
Program 6 and 7
13 ms
(1) Load current (A)
(2) Ambient temperature (
)
4.0
3.0
-20
45
50
55
(1)
(2)
Содержание MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Страница 2: ......
Страница 29: ...1 OVERVIEW 27 1 MEMO ...
Страница 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Страница 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Страница 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Страница 169: ...APPX Appendix 6 How to Use MELSEC iQ F Series Safety Extension Module Configuration Guide 167 A MEMO ...
Страница 171: ...I 169 MEMO ...
Страница 175: ......