Electrical installation
Explanation of the possible selections in operating mode 2 “single break PSDI”:
“Standard (interruption and reset)” signifies:
ESPE switches to green after protective field interruption and subsequent actuation of
the reset button
“Alternative (reset and interruption)” signifies:
ESPE switches to green after actuation of the reset button and subsequent protective
field interruption
5.3.2
LVS (450 mm and larger) on filter presses with internal switching
“with/without restart interlock”
Operating mode setting, operating mode 1 to 3:
in External device monitoring (EDM) select
“Active
”
“
check Reset button active”
in “Reset performed immediately after ...”
select “Press and release”
in “Connection of the reset button” select
“at the system plug”
Set scanning range in m to suit the distance between sender/receiver using the list box
set required operating mode as per the following table; you can obtain an additional
operating mode using “Add operating mode”
Operating mode 1:
Operating mode 2:
Operating mode 3:
“MCC-TDC sampling in protective operation”
n/a
The restart interlock
function must be set to
“Internal”
The restart interlock function
must be set to
“External”
On switching from operating mode 2 to operating mode 1 by the machine controller, the
machine is stopped, as the C4000 Standard/Advanced safety light curtain switches to the
safe state (can be seen from the illuminated red LED). The restarting of the machine must
be acknowledged by actuating the reset button.