Electrical installation
Fig. 5-6
shows the interaction between the switching outputs and the “Light path
interrupted“ LED during optical data transmission. The output circuits and the characteristic
data of the outputs are shown in
Fig. 5-7
and
Table 5-6
.
Fig.
5-6: ISD 230: Functionality of the “Light path free“ and “Contamination“ outputs
Fig.
5-7: ISD 230: Wiring of the “Light path free“ and “Contamination“ PNP outputs
“Contamination“
switching output
“Light path free“
switching output
Optical
data transmission
“Light path
interrupted“ LED
LED blinks
No contamination
Light path free
“Light path free“
GND
“Contamination“ output
circuit (pin 2):
identical to “Light path free“ output
LED off
ISD 260/280
3
2
U
V
ISD 230
5
V
S
Light reception
Full
Poor
•
The “Transmitter off“ switching input can be used to switch off the transmitter on the
unit if necessary. A voltage of +24 V must be applied for this purpose.
The input circuit and the characteristic data are shown in
Fig. 5-8
and
Table 5-7
.
Switching performance
PNP-switching against the supply voltage V
S
Properties
short-circuit-proof + temperature-protected
not electrically isolated from V
S
Electrical values
0 V
≤
V
OUT
≤
V
S
Guaranteed:
V
OUT
≤
V
S
−
1.5 V at I
OUT
≤
20 mA
I
OUT
≤
20 mA
Tab.
5-6: ISD 230: Characteristic data of the “Light path free“ and “Contamination“ switching
outputs
Fig.
5-8: ISD 230: Connection diagram of “Transmitter off“ PNP input
“Transmitter off“
GND
ISD 230
4
5
Configuration
and
electrical
installation
of
the
ISD
230