- 20 -
4.4.3
Input
Each input wiring is shown below.
Note: For DC voltage input, (+) side input terminal number of 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V
DC differs from that of 0 to 1 V DC.
Thermocouple
RTD
Direct current,
DC voltage
(0 to 1 V)
DC voltage
(0 to 5 V,
1 to 5 V,
0 to 10 V)
4.4.4
Event Output EV1, EV2 and EV3
Event output EV1 is a standard feature.
Event output EV2 is available when EV2 or EV3(DR) option is ordered.
Event output EV3 is available when EV3D
or EI option is ordered.
Specifications of Event output EV1, EV2 and EV3 are shown below.
Relay contact
1a
Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos =0.4)
Electrical life: 100,000 cycles
Minimum applicable load: 10 mA 5 V DC
Event Output EV1
Event Output EV2
Event Output EV3
4.4.5
Insulated Power Output
If P24 option is ordered, the Insulated power output is available.
Specifications of Insulated power output are shown below.
Output voltage
24 3 V DC (When load current is 30 mA DC)
Ripple voltage
Within 200 mV DC (When load current is 30 mA DC)
Max. load current
30 mA DC
Insulated Power Output