- 33 -
Process high alarm
Process low alarm
(Fig. 6-7)
(Fig. 6-8)
High limit with standby alarm
Low limit with standby alarm
(Fig. 6-9)
(Fig. 6-10)
High/Low limits with standby alarm
High/Low limits with standby independent alarm
(Fig. 6-11)
(Fig. 6-12)
• About Time signal output
Time signal output OFF time and Time signal output ON time are set within total time in one pattern.
After program control starts, Time signal output turns ON during Time signal output ON time after
Time signal output OFF time has elapsed.
During Wait action or program control Hold, progress time of Time signal output stops.
When step time is changed during program control RUN, Time signal output timing is re-calculated
using the changed pattern time.
ON
EV1 hysteresis
OFF
EV1
SV
EV1 low limit value
Alarm output is in
standby.
ON
EV1 hysteresis
OFF
EV1 value
ON
EV1 hysteresis
OFF
EV1 value
ON
EV1 hysteresis
OFF
-EV1 value
SV
+EV1 value
Alarm output is in
standby.
ON
EV1 hysteresis
OFF
SV
-EV1 value
+EV1 value
Alarm output is in
standby.
ON
EV1 hysteresis
OFF
EV1 value
SV
EV1 value
Alarm output is in
standby.