Control Performance
Control action
• PID control action (with AT function)
• PI control action (When derivative time is set to 0.)
• PD control action (When integral time is set to 0.)
• P control action (When integral and derivative time are set to 0.)
• ON/OFF control action (When proportional band is set to 0 or 0.0.)
OUT1 proportional
band (P)
Thermocouple, RTD input without decimal point:
0 to Input span
( )
Thermocouple, RTD input with decimal point:
0.0 to Input span
( )
DC voltage, current inputs:
0.0 to 1000.0%
(ON/OFF control action when set to 0 or 0.0.)
Integral time (I)
0 to 3600 sec (Setting the value to 0 disables the function.)
Derivative time (D)
0 to 1800 sec (Setting the value to 0 disables the function.)
OUT1 proportional
cycle
0.5,
1 to 120 sec
ARW
0 to 100%
OUT1 ON/OFF
hysteresis
0.1 to 1000.0
( )
DC voltage, current inputs:
1 to 10000 (The placement of the decimal point follows the selection.)
OUT1 high limit,
OUT1 low limit
0 to 100% (Direct current output: -5 to 105%)
Standard Function
Wait function
During program control, the program does not proceed to the next step
until the deviation between PV and SV enters SV Wait value at the end
of step.
The PV Display and PTN/STEP Display flash while the Wait function is
working.
Program control Hold
function
During program control RUN, progress of current step can be
suspended.
During program control RUN, if the
key is pressed for approx. 1
second, the Program control Hold function is enabled.
While the Program control Hold function is working, the PV Display and
RUN indicator flash.
Pressing the RUN key cancels suspension, and program control
resumes.
Advance function
Interrupts current step during program control RUN, and proceeds to the
beginning of the next step.
During program control RUN, if the RUN key is pressed for approx. 1
second, the Advance function is enabled.
Pattern link and
repetitions function
Patterns 1 to 10 can be linked to the next pattern (of each pattern).
For Pattern 10, Pattern 1 can be linked.
Number of repetitions for Patterns 1 to 10: 0 to 10000 times.
For repetitions of linked patterns, the whole linked pattern will be
repeated as many times as set for the former pattern.
Step SV when program
control starts
Program control starts from the step SV set in [Step SV when program
control starts].