- 51 -
• Before entering Event setting mode
Select a pattern number with the PTN key before entering Event setting mode.
• How to enter Event setting mode
In RUN mode, press the MODE key for approx. 3 seconds to enter Event setting mode.
Setting items in Event Setting mode are shown below.
Characters,
Factory Default
Setting Item, Function, Setting Range
a1//
1 ///0
EV1 alarm value
• Sets EV1 alarm value.
EV1 alarm value matches EV1 low limit alarm value in the following cases:
004 (High/Low limits independent alarm), 006 (High/Low limit range
independent alarm) or 012 (High/Low limits with standby independent alarm)
is selected in [Event output EV1 allocation].
• Setting range:
High limit alarm
-(Input span) to Input span
(*1)
Low limit alarm
-(Input span) to Input span
(*1)
High/Low limits alarm
0 to Input span
(*1)
High/Low limits independent alarm
0 to Input span
(*1)
High/Low limit range alarm
0 to Input span
(*1)
High/Low limit range independent alarm
0 to Input span
(*1)
Process high alarm
Input range low limit to Input range high limit
(*2)
Process low alarm
Input range low limit to Input range high limit
(*2)
High limit with standby alarm
-(Input span) to Input span
(*1)
Low limit with standby alarm
-(Input span) to Input span
(*1)
High/Low limits with standby alarm
0 to Input span
(*1)
High/Low limits with standby independent alarm
0 to Input span
(*1)
(*1) For DC voltage, current inputs, the input span is the same as the scaling span. (The
placement of the decimal point follows the selection.)
(*2) For DC voltage, current inputs, input range low (or high) limit value is the same as
scaling low (or high) limit value. (The placement of the decimal point follows the
selection.)
Available when
/001
(High limit alarm) to
/
(
012
High/Low limits with standby
independent alarm) is selected in [Event output EV1 allocation].
a1h/
1 ///0
EV1 high limit alarm value
• Sets EV1 high limit alarm value.
• Setting range: Same as those of EV1 alarm value.
Available when
/004
(High/Low limits independent alarm),
/006
(High/Low limit range
independent alarm) or
/012
(High/Low limits with standby independent alarm) is selected
in [Event output EV1 allocation].
t1of
1 00:00
TS1 output OFF time
• Sets TS1 output OFF time.
• Setting range:
00:00 to 99:59 (Time unit follows the selection in [Step time unit].)
Available when
/015
(Time signal output) is selected in [Event output EV1 allocation].
Содержание PCB1
Страница 1: ...PROGRAMMABLE CONTROLLER PCB1 INSTRUCTION MANUAL ...
Страница 159: ... 159 15 Key Operation Flowchart ...