- 77 -
Characters,
Factory Default
Setting Item, Function, Setting Range
evo3
/ /000
Event output EV3 allocation
• Selects Event output EV3 from the table below.
• When changing Event output EV3, refer to Section “9.6 Items to be Initialized
by Changing Settings” (p.104).
• Selection item:
/000
No event
/001
Alarm output, High limit alarm
/002
Alarm output, Low limit alarm
/003
Alarm output, High/Low limits alarm
/004
Alarm output, High/Low limits independent alarm
/005
Alarm output, High/Low limit range alarm
/006
Alarm output, High/Low limit range independent alarm
/007
Alarm output, Process high alarm
/008
Alarm output, Process low alarm
/009
Alarm output, High limit with standby alarm
/010
Alarm output, Low limit with standby alarm
/011
Alarm output, High/Low limits with standby alarm
/012
Alarm output, High/Low limits with standby independent alarm
/013
Heater burnout alarm output (When C5W, EIW or W option is
ordered):
Detects load current value with CT (current transformer), and if it is
lower than heater burnout alarm value, Heater burnout alarm
output is turned ON.
/014
Loop break alarm output:
Loop break alarm time and Loop break alarm span are set.
If the PV does not reach the span setting within the time allotted to
assess the Loop break alarm (after the MV has reached 100% or
the OUT high limit value), the alarm output is turned ON.
If the PV does not drop to the span setting within the time allotted
to assess the Loop break alarm (after the MV has reached 0% or
the OUT low limit value), the alarm output is turned ON.
/015
Time signal output:
Turns ON during program control RUN, by setting Time signal
output OFF time and ON time within total time in one pattern.
/016
Output during AT:
Turns ON during AT.
/017
Pattern end output:
Turns ON when Program control ends, and remains ON during
the time set in [Pattern end output time].
/018
Output by communication command:
Communication command 8004 B0
EV1 output
0: OFF, 1: ON
B1
EV2 output
0: OFF, 1: ON
B2
EV3 output
0: OFF, 1: ON
/019
RUN output:
Turns ON during program control RUN.