- 121 -
Program control start type
Selects program control start type.
PV start:
Only when program control starts, the step SV is advanced to the PV,
then program control starts.
PVR start:
When program control starts and in pattern repeating, the step SV is
advanced to the PV, then program control starts.
SV start:
Program control starts from the step SV which has been set in
[Step SV when program control starts].
Power restore action
If power fails during program control RUN, the controller can be
operated depending on the selection in [Power restore action].
Stops after power is restored:
Stops current program control, and returns to Program control STOP
(in Standby).
Continues after power is restored:
Continues (Resumes) previous program control after power is
restored.
Suspends after power is restored:
Suspends (on hold) current program control, and performs control
using the step SV from the point of suspension.
Pressing the RUN key cancels suspension, and program control
resumes.
Progressing time error when power is restored: 1 minute or 1 second
Step time speed-up
function
During program control RUN, makes step time progress 60 times faster
while the FAST key is pressed.
If the Wait function is set, the Wait function has priority.
Event output EV1
Output turns ON or OFF, depending on Event condition selected in
[Event output EV1 allocation]:
Alarm output, Heater burnout alarm output, Loop break alarm output,
Time signal output, Output during AT, Pattern end output, Output by
communication command, RUN output
Alarm action
Selects any alarm action in [Event output EV
allocation] from the
following:
High limit alarm, Low limit alarm, High/Low limits alarm, High/Low
limits independent alarm, High/Low limit range alarm,
High/Low limit range independent alarm, Process high alarm,
Process low alarm, High limit with standby alarm, Low limit with
standby alarm, High/Low limits with standby alarm, High/Low limits
with standby independent alarm
Alarm Energized/De-energized action are applied to the above alarms,
totaling 24 alarm types. No alarm action can also be selected.
Set value
Factory default value: 0
Action
ON/OFF action
Alarm hysteresis
0.1 to 1000.0
( )
DC voltage, current input: 1 to 10000 (The placement of the decimal
point follows the selection.)
Output
EV
output for which Alarm output (001 to 012) is selected in [Event
output EV
allocation].