- 32 -
Characters,
Factory Default
Setting Item, Function, Setting Range
/018
Output by communication command:
Communication command 8004H
B0
EV1 output
0 : OFF, 1: ON
B1
EV2 output
0 : OFF, 1: ON
B2
EV3 output
0 : OFF, 1: ON
/019
RUN output:
Turns ON during program control RUN.
When
/001
(High limit alarm) to
/012
(High/Low limits with standby independent alarm) or
/015
(Time signal output) is selected, one alarm can be set to one event output.
When
/013
(Heater burnout alarm output),
/014
(Loop break alarm output) or
/016
(Output during AT) to
/019
(
RUN output) are selected, each output is common to multiple
event outputs.
• About alarm output
EV1 alarm output actions are shown below.
High limit alarm
Low limit alarm
(Fig. 6-1)
(Fig. 6-2)
High/Low limits alarm
High/Low limits independent alarm
(Fig. 6-3)
(Fig. 6-4)
High/Low limit range alarm
High/Low limit range independent alarm
(Fig. 6-5)
(Fig. 6-6)
ON
EV1 hysteresis
OFF
SV
EV1 low limit value
ON
EV1 hysteresis
OFF
SV
+EV1 value
-EV1 value
ON
EV1 hysteresis
OFF
SV
-EV1 value
+EV1 value
ON
EV1 hysteresis
OFF
SV
EV1 value
EV1 value
ON
EV1 hysteresis
OFF
SV
EV1 low limit value
ON
EV1 hysteresis
OFF
SV
EV1 value
EV1 value