- 153 -
Characters,
Factory Default
Setting Item, Setting Range
Data
pret
/ stop
Power restore action
stop
Stops after power is restored.
After power is restored, stops current program control, and
returns to the Program control STOP (in Standby).
cont
Continues (resumes) after power is restored.
Continues (resumes) previous program control after power
is restored.
hold
Suspends after power is restored.
After power is restored, suspends (on hold) current
program control, and performs Fixed value control using
the SV from the point of suspension.
Pressing the RUN key cancels suspension, and Program
control resumes.
s_sv
/ ///0
Step SV when program control starts
Setting range: Scaling low limit to Scaling high limit (The placement of
the decimal point follows the selection.)
s_sl
/ pv//
Program control start type
pv//
PV start:
Only when Program control starts, the step SV and step
time are advanced to the PV, then Program control starts.
pvr/
PVR start:
When Program control starts and in pattern repeating, the
step SV and step time are advanced to the PV, then
Program control starts.
sv//
SV start:
When Program control starts, the Program control starts
from the step SV set in [Step SV when program control
starts].
petm
/ ///0
Pattern end output time
Setting range: 0 to 10000 seconds
at_b
/ //20
AT bias
Setting range:
Thermocouple, RTD inputs without decimal point: 0 to 50
(0 to 100 )
Thermocouple, RTD inputs with decimal point: 0.0 to 50.0
(0.0 to
100.0 )
Available when Thermocouple or RTD input is selected in [Input type].
eout
/ off/
Output status when input errors occur
off/
Output OFF
on//
Output ON
Available for direct current and voltage inputs, and direct current output.