10.1.3 When there is a Large Error
1
10.1.4 When the Trend Recording is Deflected
Flowchart 3
Trend Recording is out of range (0 or 100%)
Input signal wiring
correct?
Wire it correctly.
(See Section 4.2
on pages 17-19)
NO
(Sensor burnout, etc)
Input value and
signs (+/-) are
correct ?
Range and scale
setting correct?
NO
NO
YES
YES
YES
Input them correctly.
(See Section 4.2
on pages 17-19)
Set them correctly.
(See Section 7.1.1
on p.45)
Contact our dealer where you purchased
the instrument, or our sales representative.
Flowchart 2
Large error
Scaling setting
correct?
Calibration
correct?
Calibrate again.
(See 9.5 on p.100)
Set it properly.
(See 7.1.1 on p.48)
Zero/span position
of
chart
paper
correct?
NO
YES
YES
YES
YES
NO
NO
NO
Calibrate again.
(See 7.2.11 on
pages 81-82.)
(Dot printing error)
Contact our dealer where you purchased
the instrument, or our sales representative.
Display or printed
value matches dot
printing value?
YES