Refer to the table below to perform inspection when the equipment is operating poorly.
If you cannot resolve a problem after inspecting the equipment, request repair at the retail outlet
where the equipment was purchased.
Symptom
Possible Causes
Remedy
Starter motor does
not start.
1
.
Battery has a low charge.
2
.
Battery is deteriorated.
1
.
Recharge the battery.
2
.
Replace the battery.
Engine does not
start.
1
.
Fuel lever is "CLOSE".
2
.
No fuel
3
.
Emergency stop SW is “ON”.
4
.
Terminal covers are opened.
5
.
Water or foreign material is
mixed in with the fuel.
6
.
Blown fuse
1
.
Turn the fuel lever to "OPEN".
2
.
Add fuel.
3
.
Release Emergency stop SW.
4
.
Close the Terminal covers.
5
.
Drain water from and clean the
fuel tank and fuel strainer.
6
.
Replace the fuse.
Engine starts but
quickly stops.
1
.
Insufficient oil
2
.
Overheating of water
temperature
3
.
Battery recharging fault
1
.
Add oil.
2
.
Comply with rated outputs/Add
cooling water.
3
.
Repair.
Black or white
smoke is
continuously
exhausted from
the muffler.
1
.
Overloaded
1
.
Comply with the rated output.
Engine does not
stop.
1
.
Stop solenoid fault
1
.
Turn the fuel lever to "CLOSE"
to stop the engine and repair.
No AC power
output
1
.
Breaker is "OFF" .
1
.
Turn the breaker to "ON" .
AC power output is
weak.
1
.
The current of devices
using the equipment
exceed the rated current.
1
.
Refer to "Usable Device
Capacities" .
-43-