Configuration examples in RSLogix 5000
Configuration and Startup on the DeviceNet Fieldbus
Fill the other fields in the following sequence:
• Source Element = WriteParameterRequest.Index
• Source Length = 12
• Destination = WriteParameterResponse.Index
• Class = 7
hex
• Instance = 2
• Attribute = 4
hex
• Service Code = 10
hex
7. After downloading the changes to the PLC, index and value to be written into the pa-
rameter can be entered at
WriteParameterRequest.Index
and
WriteParameterRe-
quest.Data.
Changing the
WriteParameterStart
control bit to "1" executes the write
command once:
On response to the write request,
WriteParameterResponse.Index
should give the
written index and
WriteParameterResponse.Data
should contain the written data. In
this example, the value C8hex (200 dec) was written to the timeout interval RS485_1
(index 10228, subindex 3).
You can check the value in the MOVITOOLS
®
MotionStudio parameter tree. The
tooltip of a parameter displays for example index, subindex, factor, etc. of the
parameter.