Status and error messages
Installation Notes
4.4.3
Inverter error
In case of an inverter error, the status display alternatively shows the address/number
of the axis and 3 times the corresponding error code.
The following figure shows the display for an "Overtemperature" error of axis 1:
For a list of error codes, refer to section "Service / Error list of MOVIPRO
®
SDC"
(page 133).
4.4.4
Status LED
The status LEDs are located on the service unit of MOVIPRO
®
. They show the fieldbus
and unit status.
Status LED S1
DeviceNet
1806505867
1954344587
[1] Status LEDs S1, S2, S3
[1]
LED status
Status
Meaning
Off
•
Not switched on / offline
•
Unit is offline.
•
Unit is performing DUP MAC check.
•
Unit is switched off.
Flashing green
•
Online and in operational mode
•
The unit is online and no connection
has been established.
•
DUP-MAC check performed
successfully.
•
A connection has not yet been
established with a master.
•
Missing, incorrect or incomplete
configuration.
Lights up green
•
Online, operational mode and
connected
•
Online
•
Connection has been established with
a master.
•
Connection is active (established
state).
Flashing red
•
Minor fault or connection timeout
•
A correctable fault has occurred.
•
A unit error is active.
•
Polled I/O and/or bit-strobe I/O
connections are in timeout state.
Lights up red
•
Critical fault or critical link failure
•
A correctable fault has occurred.
•
BusOff status
•
DUP-MAC check has detected an
error.