96
Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
10
PROFINET diagnostics alarms
PROFINET IO Configuration
10.4 PROFINET diagnostics alarms
10.4.1 Switching on the diagnostic alarms
The PROFINET interface supports diagnostic alarms in the event of a unit fault. These
diagnostic alarms are deactivated by default. Proceed as follows to activate the diagnos-
tics alarms in STEP 7 HW Config:
1. Highlight slot 0.
2. Right-click on it and select 'Object properties ...' from the context menu.
A window is displayed.
3. Select the "Parameters" tab [1].
4. In 'Activate diagnostics alarms' [2], set the alarms to 'ON'
64646AXX
[1]
"Parameters" tab
[2]
'Activate diagnostics alarms' node
[1]
[2]