Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
5
Configuration examples in RSLogix 5000
Configuration and Startup (EtherNet/IP)
Only few changes are required for parameter write access:
• Create the controller tags (see following figure)
• Create a rung for executing the 'WriteParameter' command (see following figure).
For contact, select the tag "WriteParameterStart"
For message control, select the tag "WriteParameter"
• Click on
in the MSG command to open the 'Message Configuration' window
(see following figure).
Fill the other fields in the following sequence:
– Source Element = WriteParameterRequest.Index
– Source Length = 12
– Destination = WriteParameterResponse.Index
– Class = 7
hex
– Instance = 2
– Attribute = 4
hex
– Service Code = 10
hex
11771AXX
11772AXX
11773AXX