Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
57
7
Configuration of the master (Modbus scanner)
Configuration and Startup (Modbus/TCP)
Addressing the
drive using IO
scanning
• Choose the "IO Scanning" tab page. In this tab page you specify which of the stations
connected to the Modbus are to exchange cyclical data.
• In the section "Master %MW zones" enter the control memory areas that are to be
used to exchange cyclical data with the Modbus stations. You will use the memory
addresses later in your PLC program.
• Enter the following in the "Scanned peripherals" group:
– In the "IP address" input field, enter the IP address of the SEW drive.
– In the "Unit ID" input field, enter the value "0".
– In the "Repetitive rate" dropdown menu, enter the cycle time that is used to ad-
dress the stations.
– Enter the value "4" in the input fields "RD ref.slave" and "WR ref. slave" as the
cyclical process data are available from offset 4.
– In the input fields "RD count" and "WR count" enter the number of words to be
exchanged. The values must be the same in both fields. For the DHR41B option,
you can enter between 1 and 64 words.
• Click on the button "Confirm " to confirm the rack configuration and the global config-
uration.
• Once you have transferred your settings and started the program, the color of LED
L13 (NETWORK/STATUS) of DHR41B changes to green (see section 'Status LEDs
of the DHR41B option').