Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
29
5
Configuration examples in RSLogix 5000
Configuration and Startup (EtherNet/IP)
4. To copy the data of MOVI-PLC
®
advanced
DHR41B to the new data structure, a CPS
command is added at the start of the "MainRoutine" which reads the data from the
controller tag (see following figure).
To copy the data from the new data structure to MOVI-PLC
®
advanced
DHR41B, a
CPS command is added at the end of the 'MainRoutine' (see following figure).
5. Now save the project and upload it to the PLC. The PLC is set to RUN mode.
Now, the actual values can be read from MOVI-PLC
®
advanced
DHR41B and set-
points can be written.
The process data should now correspond to the values displayed in the PLC Editor
or in the diagnostics plug-in of the active IEC program in MOVITOOLS
®
MotionStu-
dio.
If there is no IEC program in MOVI-PLC
®
, you can create one as follows:
12058AXX
12059AXX
0
0
I