Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
25
5
Configuring the master (EtherNet/IP scanner)
Configuration and Startup (EtherNet/IP)
First enter the name under which the data is stored in the controller tags for the newly
created module, and then enter the IP address.
•
For the data format, open the dropdown menu "Comm-Format"and choose the
entry "Data - INT". Process data for DHR41B always contains 16 bits (INT).
• In the "Connection Parameters" group box, enter the value "171" in the "Input As-
sembly Instance" input field. The input data of the PLC must be linked to the output
instance of DHR41B.
• To establish a controlling connection, in the "Connection Parameters" group box, en-
ter the value "161" in the "Output Assembly Instance" input field. The input data of
the PLC must be linked to the output instance of DHR41B.
• In the selection fields "Input Size" and "Output Size," set a maximum value of "64"
(16 bit) as the data length.
• In the "Configuration Size" selection field, enter the value "0." The "Configuration As-
sembly Instance" input field is not used in this case.
• Click [OK] to complete the process.
• To ensure compatibility with existing DeviceNet configurations, you can also choose
the data type 'SINT' in the 'Comm Format' selection field. In this case, you must en-
sure that an even number of bytes (2 128) is configured and that data consistency
is maintained during operation when the IO data is accessed.
12062AXX
0
0
I