Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
5
Configuring the master (EtherNet/IP scanner)
Configuration and Startup (EtherNet/IP)
5.2
Configuring the master (EtherNet/IP scanner)
The following example refers to the configuration of the AllenBradley CompactLogix
1769-L32E controller with RSLogix 5000 programming software. The EtherNet/IP inter-
face is already integrated in the CPU component.
Process data
exchange
In the following configuration example, the option DHR41B is added to a project. To do
so, go to the view 'Controller Organizer' in the RSLogix 5000 program as shown in the
screenshot below (use the tree structure on the left side of the screen).
• In the "I/O Configuration" folder, select the entry "1769-L32E Ethernet Port
LocalENB" as the Ethernet communication interface. Make a right mouse click to
open the context menu and choose "New Module". The selection window "Select
Module Type" appears.
• To add option DHR41B to the project, select the entry "ETHERNET MODULE" from
the category "Communications". Confirm your selection by clicking [OK].
• The "New Module" window opens.
TIP
If a CPU without an EtherNet/IP interface is used, an Ethernet communication interface
must first be added to the I/O configuration.
11709AXX