Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
79
9
Diagnostic sequence
Fault Diagnostics for Operation on EtherNet/IP and Modbus/TCP
9
Fault Diagnostics for Operation on EtherNet/IP and Modbus/TCP
9.1
Diagnostic sequence
The diagnostic procedures described in the following section demonstrate the integra-
tion of the DHR41B option into an Ethernet network and the error analysis method for
the following problems:
• The MOVI-PLC
®
advanced
DHR41B controller is not integrated properly in the
EtherNet/IP or Modbus/TCP network
• The master (scanner) cannot specify any process data.
For detailed information about programming the DHR41B unit, refer to the "MOVI-PLC
®
"
advanced
DHE41B/DHF41B/DHR41B Controller" manual
For more diagnostic information, refer to the online status display in the EtherNet/IP
master (scanner), in the Modbus/TCP master and the corresponding online help.
Step 1: Checking the status LEDs of DHR41B and the DIP switch settings
The possible DIP switch settings are described in chapter "Setting the DIP switches".
For detailed information on the individual LED statuses, refer to chapter "Status LEDs
of the DHR41B option". The following table lists the resulting unit statuses for commu-
nication via X30-1 and X30-2 and possible causes. An 'X' indicates that the state of the
respective LED is not relevant.
In order to check and set the IP parameters, you can proceed according to section
'Setting IP address parameters' or use MOVITOOLS
®
MotionStudio.
The PING and IPCONFIG commands that you can enter via the DOS console on your
PC are further tools for checking the communication via Ethernet.
LED
L14
MODULE
STATUS
L13
NETWORK
STATUS
Operating
status
Cause
Off
Off
Off
No voltage supply.
Red
Red
Reset
DHR41B is in reset status.
Red
X
Error
Internal DHR41B fault.
Flashing
green
Off
IP-Stack
starting
If DHCP is active, the DHR41B remains in this state until
assigned an IP address.
Flashing
red
Red
IP conflict
IP address conflict if the same IP address is used by another
station in the network.
Flashing
green/red
Flashing
green/red
LED test
All LED conditions are briefly activated.
Flashing
green
Flashing
green
Application
starting
All functions of the DHR41B (e. g. process data and connec-
tions to the master) are now active.
Green
Flashing
green
Operational
DHR41B is active on the fieldbus but without a controlling
connection to the master.
Green
Green
Connected
There is a controlling connection to a master.
Green
Flashing red
Timeout
A previously controlling connection is in timeout state.