Installation Instruction
PIUMA MILLENNIUM
PARAMETERS
DEFAULT VALUE
ADJUSTMENT GAP
ADJUSTMENT VIA
ADVANCED
SELECTOR
PC
ST
AND
ARD
Opening speed (°/s)
60 (45)
20
60 (45)
•
•
Closing speed (°/s)
30 (20)
20
40 (20)
•
•
Pause time (sec)
0
0
120
•
•
Anti-crush Opening
9
1
9
•
•
Anti-crush Closing
9
1
9
•
•
AD
V
ANCED
Approach speed (°/s)
6
5
10
•
Reset speed (°/s)
12
10
20
•
Recovery speed (°/s)
15
10
30
•
Normal acceleration (°/s2)
150
50
200
•
Normal deceleration (°/s2)
40
20
60
•
Reset acceleration (°/s2)
40
20
100
•
Reverse acceleration (°/s2)
150
50
200
•
Approach Closing (°)
25
20
40
•
Approach Opening (°)
20
15
30
•
Anti-draught level
1
0
9
•
Push & Go activation
5
0
9
•
Asynchronous opening of double doors
3
1
9
•
Asynchronous closing of double doors
5
1
9
•
Safety exclusion opening (%)
30
0
100
•
•
Last battery-operated manoeuvre
stop open
stop open
stop close
•
•
Auto Reset
yes
yes
NO
•
•
Logic after Reset
stop close
2 radar, 1 radar, stop open, stop close
•
•
SAFE OPEN operation
stop motion
stop motion
slow motion
•
•
Setting parameter
Operating Logic
Operations
Description
WARNING
If no optional operation lock device is installed, make sure the KEY input is short circuited with the COM
input. Otherwise the equipment cannot be started.
If no safe close device is installed, make sure the SAFE CLOSE input is short circuited with the COM input.
Otherwise the equipment cannot be started.
In the event of a power failure, the equipment can be started or reset using the power supply provided by
the battery, if present. The speed, in case of battery operation, will be reduced.
Power
Position doors ~20 cm from total closure. Turn on the power switch to power the equipment.
Reset and auto-setting of
ends-of-stroke
The device is switched on and the reset phase checked. The device completely opens and completely clo-
ses the door at low speed (reset speed). If an obstacle prevents the door from completing its entire stroke,
the device will signal that there is an initialization error (AV=intermittent and L3=On) if the stroke is less than
a preset limit (around 70-80°) and performs another reset after 10 seconds. After the third failed reset, the
device stops functioning as a malfunction. The reset continues even if the safety sensor (Safe Open) detects
an obstacle. If the IR photocell sends a signal that an obstacle has been detected whilst the door is closing,
the door will stop moving for the entire duration of the signal.
Multi-logic selector not installed:
when the equipment finishes limit reset it is ready to work in 2 RADAR
logic.
Multi-logic selector installed:
when the equipment finishes limit reset it is ready to work and is positioned
in the “STOP CLOSED” logic.
The values in parentheses refer to the setting J2=ON for heavy doors.