Installation Instruction

17

PIUMA MILLENNIUM

* NA = Normally open   NC = Normally closed

The electrical signal from external peripherals can be varied through the advanced selector or PC connection: from nor-
mally closed to normally open and vice versa. See the advanced selector used manual for further details.

G. Connector for PC - unit connections

A PC connection board (optional) is required to connect the MILLENNIUM unit to a Personal Computer.
The following is possible with MILLENNIUMWARE software:

Advanced adjustments of some operating parameters

Diagnostics and advanced information on unit status

Microprocessor programming

PC connection board

Fig. 28

SIGNAL

TYPE * DESCRIPTION

FUNCTION 

COM

Common electrical signal.

SAFE CLOSE

NC

Signal for the connection of an external
photocell or safety control device for
door closing

If the door is closing and the contact opens, the unit sends and
immediate motion inversion command. Closing will only recom-
mence after the contact closes.

The signal must be short circuited with COM if not devices
(internal or external) are connected.

AUX IN

NA

Auxiliary input signal. Auxiliary devices
can be connected to this signal. It is
normally used for inter lock functions.

When used as an auxiliary signal the function logic can be per-
sonalised according to customer requests.
When used as inter lock logic, closing this signal inhibits door
functions that will not open even with open signal presence.

AUX OUT

Auxiliary output signal, PNP transistor
type for particular door condition sig-
nals (reset, open, closed, etc).

According to the type chosen signal, the output becomes active
(12Vdc and led on) when the door is in the set condition (Reset,
open, closed, etc). See the advanced selector manual for further
details.

SAFE OPEN NA

Signal for the connection of sensors for pro-
tection during door opening.

If the door is opening and the contact closes, the unit sends an
immediate movement stop command. Opening will only continue
after this signal is deactivated.

KEY

NC

Lock signal. Closure devices can be
connected such as electronic key, key
selector, transponder, etc.
The signal can be controlled in bi or
mono-stabile mode with an activation
time equal to about 500 msec. For
mode type selection see paragraph

FIRST INPUT MODE SELECTION

.

If the signal opens the unit sends a complete door closure com-
mand (from any position) From this moment until the signal is
closed the door stays in this position and no external peripheral is
detected (including multi-logic selectors). As soon as the signal
closes the door opens permitting access.

The signal must be short circuited with COM if no devices are
connected.

START 1

NA

Opening signal. Door opening devices
can be connected.

Closing this signals causes the doors to open.  This signal is only
monitored in 2 Radar logic.

START 2

NA

Opening signal. Door opening devices
can be connected.

Closing this signals causes the doors to open. This signal is moni-
tored in both 2 Radar and 1 Radar logic.

Содержание Puma Millenium

Страница 1: ...Automatic Operator for swinging doors I N S T A L L A T I O N I N S T R U C T I O N...

Страница 2: ...2...

Страница 3: ...nction page 18 Dip Switch Function page 18 Electric Lock selection page 19 Selection of the type of arm page 19 Selection of the door weight page 19 Low Power mode selection page 20 MultiSlave Selecti...

Страница 4: ...le if parts within the automatism are altered or tampered with or if safety devices other than those indicated by the manufacturer are used in the system The automatism installer must provide the auto...

Страница 5: ...truded aluminium alloy fastening base B Extruded aluminium alloy cover C Aluminium end sides Flat steel end sides option D Gear motor unit E SESAMO MILLENNIUM Electronic control panel F Transformer G...

Страница 6: ...tism is available in two configurations with standard heads in aluminium L 810 mm and with flat heads optional in steel L 800 mm Standard End Sides Flat End Sides opzionali Fig 5 Fixing Holes Std End...

Страница 7: ...guide Fig 6 The heights of the prepa red fastening holes are shown in Fig 4 and 5 For right hand opening doors anticlockwise direc tion the assembly of the automatism perfectly mir rors the left hand...

Страница 8: ...is installed on the approach side of the door the side opposite the swing side For left hand opening doors door opening with anti clockwise rotation position the automation as shown in Fig 8 using the...

Страница 9: ...ig 10 Part D by pulling it outwards To facilitate the fastening of the automatism it is possible to remove the heads Fig 11 Part A and move or remove the internal components if necessary by operating...

Страница 10: ...tor Fig 14 part A Assemble the articulated push arm Fig 14 part B to the upper hexagon with the flathead screw M6x70 supplied Fig 14 part C after having interposed the washers 6 4x12 Fig 14 part D as...

Страница 11: ...ve shaft inside the guide and distribute a uniform layer of grease on the sliding area Subsequently once the installation of the rigid arm Fig 16 part E described in a previous section is finished scr...

Страница 12: ...A using the screws supplied Fig 18 Part C WARNING check that when the door is completely open the opening of the arm does not exceed 140 If the stop does not come in contact turn the shaped plate ove...

Страница 13: ...r fixing of the automatism on the wall Check correct tightening Check that the wires are fixed and that no wire pass near the movement area Check that the arm is solidly fixed to the door and that it...

Страница 14: ...minal board must be performed with the power disconnected to prevent irreparable damage to the electro nic equipment WARNING Any repairs or replacements must be performed by professionally qualified p...

Страница 15: ...per between Millennium and external cell amplifier The system has three selectable working models A Millennium amplifier only Jumper close towards INT B External amplifier only Jumper close towards EX...

Страница 16: ...ructions for use E External peripheral power connector 12 Vdc 6W max 500mA Real power value may vary from 12 Vdc to about 15 Vdc depending on the resistive load situations connected to these terminals...

Страница 17: ...ns that will not open even with open signal presence AUX OUT Auxiliary output signal PNP transistor type for particular door condition sig nals reset open closed etc According to the type chosen signa...

Страница 18: ...t 100kg J3 Cyclic Operation Standard Operation J4 J1 Selection of the electric lock power supply voltage J2 Selection of the door weight J3 Cyclic operation only for tests J4 Not used To set the jumpe...

Страница 19: ...per according to the following diagram J2 OFF DEFAULT J2 ON J2 WARNING For safety reasons doors weighing more than 100 kg J2 ON have a maximum opening and closing speed self limited respectively to 50...

Страница 20: ...indicated below The selector can act on each of the three automatisms in a completely independent manner WARNING The Multislave logic is NOT available for Piuma Doppio 20 Installation Instruction PIU...

Страница 21: ...rmal Closing device readings Operation t 0 1 Stop Normal Closing device readings Operation t 5 0 0 m s t 5 0 0 m s t 5 0 0 m s t 5 0 0 m s S6 OFF Normal Mode Default In the event of power failure the...

Страница 22: ...Slave S1 ON S2 OFF S3 ON Enter double Master door with synchronised door motion S1 OFF S2 OFF S3 ON Enter double Slave door with synchronised door motion Synchronised Indipendent Door Motion Piuma Dop...

Страница 23: ...area Make sure that the anti crushing sensitivity in opening is not too low Check the encoder the connection between the encoder and mother boards Inversion error 5 BL OFF ON OFF ON An inversion error...

Страница 24: ...ircuited with the COM input Otherwise the equipment cannot be started In the event of a power failure the equipment can be started or reset using the power supply provided by the battery if present Th...

Страница 25: ...ts START1 and START2 of the electronic control card are not monitored if present the electric locking system blocks the door doors Stop Open The automatism controls the complete opening of the door do...

Страница 26: ...se when both are wide open If one door opens completely before the other one it will wait until the latter is completely open Both doors reverse at the same time START 1 or 2 SAFE CLOSE anti crush saf...

Страница 27: ...unit B connect the terminal AUX OUT of unit A to the terminal AUX IN of unit B connect terminal of the 12Vdc power supply of unit A to the terminal of the 12Vdc power supply of unit B Use 4 x 0 22 shi...

Страница 28: ...SESAMO srl Str Gabannone 8 10 15030 Terruggia AL Italy Tel 39 0142 403223 Fax 39 0142 403256 www sesamo eu E mail info sesamo eu MAN_PIM_EN_2_04_08...

Отзывы: