Adjustments to be made regularly
Adjustment
of the MIN and
MAX
value
The MIN and MAX value is the lowest respectively highest value that is allowed for the supply line temperature.
Adjusting the minimum and maximum supply line temperature is particularly important if your home has floor
heating.If your house has floor heating and parquet floor, the supply line temperature should not be higher than 45°C.
Else the floor might get damaged. If you have floor coils and stone tiles, the MIN value should be 22-25°C in summer
when no heating is required – to obtain a comfortable floor temperature.
If there is a basement to your house, the MIN value should be adjusted to a suitable temperature in summer too, to
avoid a humid and chilly basement. In such cases,the value for HEAT STOP needs being adjusted upwards.
If you wish to change the MIN or MAX value:
1 Open the main menu INFORMATION by pressing the right- or left-hand button once.
You will find the cursor at the sub-menu OPERATION
2 Press the ”down” button to move the cursor to the sub-menu HEAT CURVE
3 Open the selected menu by pressing the right-hand button once. You will find the cursor at the parameter
CURVE.
4 Press the ”down” button to move the cursor to MIN.
5 Open the selected parameter by pressing the right-hand button once. The cursor is at MIN
6 Raise or lower the value, using the ”up” and ”down” button respectively.
7 Press the left-hand button three times to return to the main menu.
Repeat the procedure to change the MAX value, replacing MIN by MAX at step 4.
Control
35
Adjustment of
the
HEAT
STOP
value
The HEAT STOP function stops all production av radiator heat when the outside air temperature is equal to or
higher than the value entered for heat stop.When the heat stop function is activated, the circulation pump will be
turned off except when warm water is being produced. Even if shut off, the pump will be”exercised” during 1 minute
a day. Factory setting for heat stop is 17°C.( 0~ 24°C adjustable )
If you wish to change the HEAT STOP value:
1 Open the main menu INFORMATION by pressing the right- or left-hand button once.
You will find the cursor at the sub-menu OPERATION
2 Press the ”down” button to move the cursor to the sub-menu HEAT CURVE
3 Open the selected menu by pressing the right-hand button once.
4 You will find the cursor at the parameter CURVE.
5 Press the ”down” button to move the cursor to HEAT STOP
6 Open the selected parameter by pressing the right-hand button once. The cursor moves to HEAT STOP
7 Raise or lower the value, using respectively the ”up” or ”down” button.
8 Press the left-hand button three times to return to the main menu.
Содержание AWA-SS-10
Страница 2: ......
Страница 21: ...Electrical connection 19 Wiring Diagram 230V 50 HZ ...
Страница 22: ...Electrical connection 20 Wiring Diagram 3X400V 3 50 HZ ...
Страница 46: ...44 1 11 3 2 4 5 6 7 9 10 12 13 14 8 9 Component placement Please Note The picture for reference only ...
Страница 48: ...Component placement 3X400 V 3 50 HZ 230 V 50 HZ 70 71 70 71 46 Please Note The picture for reference only ...