Pipe connections
8
Pipe installation must be carried out in accordance
with current norms and directives. The heat pump can
operate up to a return temperature of about 58* °C
and an outgoing temperature of about 70* °C from the
heat pump. The compressor produces up to 65* °C,
the rest is obtained using additional heating.
The other heat pumps has a max return temperature
of approximately 50 °C and an outgoing max tempera-
ture from the heat pump of approximately 60 °C.
Since the AWA,AWB series is not fitted with shut-off
valves, these must be fitted outside of the heat pump
to make future servicing easier.
During assembly the pipes for the heat medium
and water heater and possibly hot water circulation
are routed backwards. The distance between
AWA-SS series and the wall ought to be 50 mm.
General
NOTE!
The pipe system needs to be flushed
out before the heat pump is connected
so that debris cannot damage
component parts.
The size of the outlet for connecting copper pipe can be
adjusted by the fixing board.
Copper pipe connections
According to their practical situation,users can choose
the place on mainframe ( left or right ) for the out
of connecting copper pipe.
NOTE!
defrosting temperature sensor and outside
temperature sensor should be connected
outlet of mainframe and outdoor
Copper tuble size
to outdoor unit through the connecting
unit.
/
/
/
Modle
Size
AWA-
SS-
6
AWA-
SS-
8
AWA-
SS-
10
AWA-
SS-
12
AWA-
SS-
16
Gas
rör
1/
2"
5/
8"
5/
8"
3/
4"
3/
4"
Vätske
rör
1/
4"
3/
8"
3/
8"
1/
2"
1/
2"
Содержание AWA-SS-10
Страница 2: ......
Страница 21: ...Electrical connection 19 Wiring Diagram 230V 50 HZ ...
Страница 22: ...Electrical connection 20 Wiring Diagram 3X400V 3 50 HZ ...
Страница 46: ...44 1 11 3 2 4 5 6 7 9 10 12 13 14 8 9 Component placement Please Note The picture for reference only ...
Страница 48: ...Component placement 3X400 V 3 50 HZ 230 V 50 HZ 70 71 70 71 46 Please Note The picture for reference only ...