USER MANUAL – Z-PASS1/Z-PASS2
81
Some more explanations are needed for “Gateway Tag Mode” parameter.
Tags with Mode=GATEWAY are handled in the “classic” Modbus Gateway way, that is tags are read
periodically, even if no Modbus read request is received for those tags on the Modbus TCP/IP side.
Tags with Mode=BRIDGE are read only when a Modbus read request is received for those tags on the
Modbus TCP/IP side.
Instead, for write operations, tags with Mode=GATEWAY and tags with Mode=BRIDGE are handled in the
same way, that is tags are written only when a Modbus write request is received for those tags on the
Modbus TCP/IP side.