U.6.29
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Testing and Troubleshooting
Checking Relay Operation
For more information on the directional elements, see
Element on page R.1.21 in the Reference Manual
and
Distance Elements on page R.1.51 in the Reference Manual
. For settings and
application information, see
Section 1: Protection Application Examples in
.
Checking the Negative-Sequence Directional Element (Phase Faults)
NOTE:
As you perform this test,
other protection elements can assert.
This causes the relay to assert other
targets and possibly close control
outputs. Be sure to isolate the relay
from the power system to avoid
unexpected system effects.
This test confirms operation of the F32Q and the R32Q negative-sequence
directional elements. This test procedure is for a 5A relay; scale values
appropriately for a 1A relay.
This example assumes that you have successfully established communication
with the relay; see
Making an EIA-232 Serial Port Connection on page U.4.6
for a step-by-step procedure. In addition, you must be
familiar with relay access levels and passwords. See
Passwords on page U.4.8 in the User’s Guide
to change the default access
level passwords and enter higher relay access levels. You should be familiar
with the
AC
SEL
ERATOR
software, see
Section 3: PC Software in the User’s
.
Step 1. Configure the relay. Begin the
AC
SEL
ERATOR
software and
read the present configuration in the SEL-421 Relay. On the
Settings menu, click Read. The relay sends all settings and
configuration data to the
AC
SEL
ERATOR
software. Expand the
Group 1 settings and click the Relay Configuration branch of
the Settings tree view as shown in
. Confirm
Directional Element Control E32 is AUTO.
Disable element supervisory conditions. Select the Relay
Configuration button in the
AC
SEL
ERATOR
software Settings
tree view. Confirm that ELOAD and ELOP are set to N.
Figure 6.23
Group 1 Relay Configuration Settings:
AC
SEL
ERATOR
Software.
Содержание SEL-421
Страница 8: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 110: ...This page intentionally left blank ...
Страница 204: ...This page intentionally left blank ...
Страница 284: ...This page intentionally left blank ...
Страница 286: ...This page intentionally left blank ...