![Sel SEL-421 Скачать руководство пользователя страница 186](http://html1.mh-extra.com/html/sel/sel-421/sel-421_user-manual_1236405186.webp)
U.4.56
SEL-421/SEL-421-1 Relay
User’s Guide
Date Code 20020501
Basic Relay Operations
Operating the Relay Inputs and Outputs
Step 6. Set OUT105 to respond to Local Bit 3. Type
SET O
OUT105<Enter>
(See
). At the ? action prompt,
type
LB03<Enter>
. At the next ? action prompt, type
END<Enter>
. When prompted to save settings, answer
Y<Enter>
.
=
>>
SET O OUT105<Enter>
Output
Main Board
OUT105 :
==
NA
?
LB03<Enter>
OUT106 :
=
NA
?
END<Enter>
Output
Main Board
OUT101 :
=
3PT AND NOT PLT04
OUT102 :
=
3PT AND NOT PLT04
OUT103 :
=
BK1 CL AND NOT PLT04
OUT104 :
=
KEY AND PLT02 AND NOT PLT04
OUT105 :
=
LB03
OUT106 :
=
NA
OUT107 :
=
PLT04
OUT108 :
=
NOT (HALARM OR SALARM)
Save settings (Y,N) ?
Y<Enter>
Saving Settings, Please Wait...........
Settings Saved
=
>>
Figure 4.51
Setting Control Output OUT105: Terminal.
Step 7. Test the connection and programming. Use the appropriate
interface hardware to connect the fan control start circuit to
OUT105. At the relay front-panel MAIN MENU, select
LOCAL CONTROL and press the
{ENT}
pushbutton (See
). Select 5 MVA XFMR Fans on the LOCAL
. Press
{ENT}
to
see the last screen of
. Highlight “1 ON” and press
{ENT}
. The graphical local control handle moves to the 1
position. At this time, the transformer fans will begin running.
Содержание SEL-421
Страница 8: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 110: ...This page intentionally left blank ...
Страница 204: ...This page intentionally left blank ...
Страница 284: ...This page intentionally left blank ...
Страница 286: ...This page intentionally left blank ...