U.4.32
SEL-421/SEL-421-1 Relay
User’s Guide
Date Code 20020501
Basic Relay Operations
Examining Metering Quantities
=
>>
SET CTRW TERSE<Enter>
Group 1
Line Configuration
Current Transformer Ratio - Input W (1-50000) CTRW :
=
1000 ?
200<Enter>
Current Transformer Ratio - Input X (1-50000) CTRX :
=
1000 ?
<Enter>
Potential Transformer Ratio - Input Y (1-10000) PTRY :
=
2000 ?
END<Enter>
Save settings (Y,N) ?
Y<Enter>
Saving Settings, Please Wait...........
Settings Saved
=
>>
Figure 4.22
Setting CTRW and PTRY: Terminal.
Step 5. Turn relay power off.
Step 6. Connect analog inputs. If three voltage sources and three
current sources are available, connect the sources to the relay as
shown in
. If three voltage sources and two current
sources are available, use the connection diagram of
. Apply 67 V per phase (line-to-neutral) in ABC
phase rotation. Apply 2.0 A per phase, in phase with the
applied phase voltages.
Figure 4.23
Test Connections Using
Three Voltage Sources/Three Current Sources.
Three-Phase
Voltage and Current
Test Sources
IA
VB
IB
VC
IC
VA
IAW
Z01
Z02
Z03
Z04
Z05
Z06
Z13
Z14
Z15
Z16
Z17
Z18
IBW
ICW
VAY
VBY
VCY
Relay Rear-Panel Analog
Voltage and Current Inputs
Содержание SEL-421
Страница 8: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 110: ...This page intentionally left blank ...
Страница 204: ...This page intentionally left blank ...
Страница 284: ...This page intentionally left blank ...
Страница 286: ...This page intentionally left blank ...